RT95: RTD Transmitter Vietnam
Linearizing for Pt100 sensor
- Programmable range - Isolated input to output to Power Supply - True lead length compensation |
RTD Transmitter RT95 are compactly designed for converting the variations of resistance in a Pt100 temperature sensor to a linearized and isolated DC. voltage or current output. They provide constant current excitation and true lead length compensation when used with a 3-wire RTD, which can be located at a considerable distance from the transmitter.
RTD Input |
|
---|---|
Number of channel: |
1 Channel |
Input type: |
Pt100 DIN or JIS (3 Wire Connection) |
Input range: |
Rangeable zero from - 100 °C to +100 °C |
Rangeable span from 15 °C to 500 °C |
|
Other types of RTD input available Cu 100, Pt 1000 |
|
Input impedance: |
Lead wire resistance 5 ohm/wire max. |
Analog Output |
|
---|---|
Number of channel: |
1 Channel |
Output type: |
Current, Voltage |
Output range: |
Current (4 to 20 mA) |
Voltage (0 to 5, 1 to 5, 0 to 10 VDC) |
|
Linearity: |
< ± 0.2% of span |
Output Load Resistance: |
Current (Max 1000 Ω load) |
Voltage (Min. 1000 Ω load) |
|
Isolation voltage: |
500 VAC Between input,output and power supply (1min. test) |
Power Requirements |
|
---|---|
Power Supply: |
100, 110, 220 VAC |
24 VDC (Optional) |
Environmental Limits |
|
---|---|
Operating Temperature: |
0 to 55 °C |
Operating Humidity: |
5 to 95 %RH |
Storage Temperature: |
0 to 70 °C |
Physical Characteristics |
|
---|---|
Dimension: |
W50 x H70 x D130mm. |
Mounting: |
Wall or DIN rail |
Connection: |
Plug-in 11 pins socket |
Warranty |
|
---|---|
Warranty Period: |
5 year |
Ordering Information: | Specify sensor type, input range, output, power supply |
Example | RT95/Pt 100/0-200 C/4-20 mA/220 VAC |
Package Checklist
1. RT95