TT37: Thermocouple Transmitter Vietnam
| - Wide programmable input range
- Linearized - Available Thermocouple in J,K,L,R,S,T - Isolated input to output - Compact DIN rail mount enclosure - High accuracy - Low cost - Easy to install |

|
Thermocouple Input |
|
|---|---|
|
Number of Channel: |
1 Channel |
|
Input Type: |
J, K, L, R, S, T |
|
Input Range: |
type J 0 to 600 °C |
|
type K 0 to 1200 °C |
|
|
type L 0 to 600 °C |
|
|
type R 0 to 1700 °C |
|
|
type S 0 to 1700 °C |
|
|
type T 0 to 400 °C |
|
|
(Units are rangeable within type of thermocouple supplied but not between different thermocouple types) |
|
|
Cold junction compensation range: |
0 to 50 °C |
|
Burn Out thermocouple: |
Upscale drive standard |
|
Analog Output |
|
|---|---|
|
Number of Channel: |
1 Channel |
|
Output Type: |
Current (2 Wire) |
|
Output Range: |
4 to 20 mA |
|
Loop Powered: |
12 to 35 VDC |
|
Linearity: |
< ± 0.25% of span (for J, K thermocouples) |
|
< ± 0.5% of span (for other types) |
|
|
Ambient drift: |
< ± 0.02% / °C of span |
|
Output Impedance: |
600 Ω @ 24 VDC (50 Ω/V above 12 VDC |
|
Isolation Voltage: |
500 VAC input/output isolation (1 min. test) |
|
Maximum Output Current: |
< 26 mA |
|
Environmental Limits |
|
|---|---|
|
Operating Temperature: |
0 to 55 °C |
|
Operating Humidity: |
5 to 95 %RH |
|
Storage Temperature: |
0 to 70 °C |
|
Physical Characteristics |
|
|---|---|
|
Dimension: |
W22 x H80 x D85 mm. |
|
Mounting: |
DIN Rail |
|
Warranty |
|
|---|---|
|
Warranty Period: |
5 year |
| Ordering Information: | Specify thermocouple type, temperature range |
| Example | TT37/Type K /0-500 °C |
Package Checklist
1. TT37