TT98: Thermocouple Transmitter Vietnam
Programmable range
- Linearized output standard signal - 2 Isolated outputs - Isolation of input, output and power supply - Cold junction compensation |
Thermocouple Transmitter TT98 The thermocouple’s signal is linearized and cold – junction compensated to provide an isolated and linearized DC. voltage or current output. Typically the TT 98 interfaces with recording, monitoring or controlling instruments.
Thermocouple Input |
|
---|---|
Number of channel: |
1 Channel |
Input type: |
Thermocouple |
Input range: |
Type J 0 to 800 °C |
Type K 0 to 1200 °C |
|
Type R 0 to 1700 °C |
|
Type S 0 to 1700 °C |
|
Type T (-)200 to 200 °C |
|
Cold junction compensation: |
0 to 50 °C |
Burn out thermocouple: |
Upscale drive standard |
Analog Output |
|
---|---|
Number of channel: |
2 Channels |
Output type: |
Current, Voltage |
Output range: |
Current (0 to 20, 4 to 20 mA) |
Voltage (0 to 1, 0 to 5, 1 to 5 VDC) |
|
Linearity: |
< ± 0.2% of span |
Output Load Resistance: |
Current (max. 1000 Ω load) |
Voltage (min 1000 Ω load) |
|
Isolation voltage: |
500 VAC (1 min.) between input, output, power supply |
Power Requirements |
|
---|---|
Power Supply: |
100, 110, 220 VAC |
24 VDC (Optional) |
Environmental Limits |
---|
Environmental Limits |
|
---|---|
Operating Temperature: |
0 to 55 °C |
Operating Humidity: |
5 to 95 %RH |
Storage Temperature: |
0 to 70 °C |
Physical Characteristics |
|
---|---|
Dimension: |
W50 x H70 x D130 mm. |
Mounting: |
Wall or DIN rail |
Connection: |
Plug-in 11 pins socket |
Warranty |
|
---|---|
Warranty Period: |
5 year |