modules-w-ext-communication-3.png

Description

  • Real time clock with battery backup.
  • 1024 Kbytes in circuit programmable FLASH memory for user program.
  • 2048 Kbytes in circuit programmable FLASH memory for user data.
  • 480 Kbytes RAM memory with battery backup for user data (2 Kbytes of RAM reserved for system variables)
  • Built-in replaceable lithium battery.
  • LED state indicators.
  • Low power consumption.
  • Process-Pascal programmable.
  • Automatic checksum control of program memory after each Reset.
  • EMC approved (89/336/EEC).

APPLICATION
A PD 600 DPI is used to provide local programmable intelligence and act as a gateway between the standard P-NET system (RS485) and the local cluster via Light-Link P-NET.
It uses either the BM 002, or the BM 010 Base Module.

The PD 600 DPI is programmed in Process-Pascal, which is an extension of standard Pascal, allowing easy declaration and utilisation of P-NET variables and objects. Programs are developed and compiled on a standard PC, then downloaded directly via a P-NET interface. Program code can be downloaded to FLASH memory.

 

SPECIFICATIONS
Communication
The PD 600 has 2 standard P-NET Communication Channels.
Channel 1 is a standard P-NET RS485 communication channel for communicating with other P-NET devices outside the cluster, i.e. the rest of the system.
Channel 2 is a P-NET Light-Link communication channel intended for communicating with other locally mounted P-NET devices using the optical Light-Link interface.

Memory
Program FLASH: 1024 Kbytes
Data FLASH: 2048 Kbytes
RAM 480 Kbytes

Power Specifications
Power Supply DC: nom. 24.0 V
min. 15.0 V
max. 32.0 V
Ripple: max. 5%

Power consumption @ 24Vdc
Operating: max. 50 mA
Current at power up: max. 100 mA

Battery Backup (RAM and RTC)
Replaceable battery (Panasonic) BR1632
Replace battery every 5 years. If the operating ambient temperature is over 50°C, replace battery more frequently.
Backup time @ 25°C typ. 1 year

Environmental Conditions

Ambient Temperature
Operating temperature: -25 °C – 70 °C
Storage temperature: -40 °C – 85 °C

Humidity
Relative humidity: max. 95%

Real Time Clock
Accuracy: Deviation is approx. 3 minutes per month over the full
temperature range.
Deviation is approx. 1 minute per month at 25 °C

Approvals
EMC EN61000-6-2, EN61000-6-3

Vibration IEC 60068-2-6
Frequency range: 2-100 Hz
Frequency / amplitude: 2-10 Hz: +/- 5.0 mm
10-100 Hz: +/- 2g
Sweep rate: max. 1 octave/min
Number of axes: 3 mutually perpendicular

Mounting requirements
The PD 600L DPI must be mounted in a metal enclosure/panel