CT195: Current Transducer (3 phase) Vietnam
Current Input 0-1 Aac, 0-5 Aac
- Analog Output 4-20 mA, 0-5 VDC, 0-10 VDC |
Current Transducer CT195 is designed for converting 3 phase sinusoidal alternating current into a load independent DC output signal proportional to the measured RMS. input values.
Input |
|
---|---|
Number of Channel: |
3 Channels |
Input Type: |
Current (3 Phase) |
Input Range: |
0 to 1, 0 to 5 Aac |
(Overrange 120% Continuously,200% for 10 sec) |
|
Input Loss: |
1 VA Max. |
Analog Output |
|
---|---|
Number of Channel: |
3 Channels |
Output Type: |
Current, Voltage |
Output Range: |
Current Max 0 to 1 mA (Load Resistance 10 KΩ) |
Current Max 0 to 5 mA (Load Resistance 2 KΩ) |
|
Current Max 0 to 10 mA (Load Resistance 1 KΩ) |
|
Current Max 0 to 20 mA (Load Resistance 600 Ω) |
|
Current Max 4 to 20 mA (Load Resistance 600 Ω) |
|
Voltage Min 0 to 10 mVDC (Load Resistance 500 Ω) |
|
Voltage Min 0 to 100 mVDC (Load Resistance 500 Ω) |
|
Voltage Min 0 to 1 VDC (Load Resistance 500 Ω) |
|
Voltage Min 0 to 5 VDC (Load Resistance 1 KΩ) |
|
Voltage Min 1 to 5 VDC (Load Resistance 1 KΩ) |
|
Voltage Min 0 to 10 VDC (Load Resistance 2 KΩ) |
|
Linearity: |
± 0.5 % of span |
Power Requirements |
|
---|---|
Power Supply: |
110, 220 VAC |
Environmental Limits |
|
---|---|
Operating Temperature: |
0 to 55 °C |
Operating Humidity: |
5 to 95 %RH |
Storage Temperature: |
0 to 70 °C |
Physical Characteristics |
|
---|---|
Dimension: |
W132 x H132 x D162 mm. |
Mounting: |
Wall Mount |
Wiring: |
Screw Terminals |
Warranty |
|
---|---|
Warranty Period: |
5 year |
Ordering Information: | Specify Input, Output, Power supply |
Example | CT195/0-5 A/4-20 mA/220 VAC |
Package Checklist
1. CT195