AQUADMS Water Disinfection Measuring System_Hệ thống đo lường khử trùng nước
Xuất sứ: Thụy Sỹ
Nhà cung cấp: Pitesco
Hãng sản xuất: Sigrist photometer
Water Disinfection Measuring System
The measuring system includes everything needed for disinfectant measurement: instrument, sensor, assembly and wiring pre-mounted on a measuring panel. The system is used for measuring free Chlorine, Chlorine dioxide, Ozone or Hydrogen Peroxide. Measuring parameter and measuring range can be chosen in the menu. The integrated armature ensures a constant flow of approx. 30 l/h. As a consequence the system provides stable, precise and reliable measuring values. Flow fluctuations are not any longer shown up in the measuring curves as long as a water inlet flow of above 35l/h is guaranteed. For measuring free Chlorine, Chlorine Dioxide or Ozone a double gold sensor is used, for measuring in brine a special graphite-platinum sensor is available. For the measurement of Hydrogen Peroxide, a double platinum sensor is used. Temperature and flow is guarded by a further sensor, which additionally can be used for grounding. The control unit with touch screen operation includes an input for the measurement and temperature, one digital input, one analogue output and alarm relay, as well as an automatic sensor cleaning. Optionally, a system with integrated pH-measuring electrode is available which compensates pH fluctuations. The complete system is pressure resistant up to 6 bars at 20°C.
More…
- Complete, pre-mounted measuring panel: mounting – water connection – measure
- Stabilized water flow
- Fast results, measurement is directly made in the medium
SPECIFICATION
Double gold & graphite sensor
Measuring principle: Potentiostatic measurement
Nominal range:
- Free Chlorine 0 .. 20 mg/l
- Chlorine Dioxide 0 .. 20 mg/l
- Ozone 0 .. 10 mg/l
- Temperature: -30 .. +140° C
Scale ranges:
- 0 .. 1’000 µg/l; 0 .. 5 / 10 / 20 mg/l Cl2 or ClO2
- 0 .. 1’000 µg/l; 0 .. 5 / 10 mg/l O3
Accuracy: ±2% of measuring range limit
Resolution: 0.01 mg/l
pH range: 6 .. 9 (free Chlorine: 6 .. 8 constant)
Double platinum sensor
Measuring principle: Potentiostatic measurement
Nominal range:
- Hydrogen Peroxide 0 .. 30 mg/l
- Temperature -30 .. +140° C
Scale range: Fix, 0 – 30 mg/l H2O2
Accuracy: ±2% of measuring range limit
Resolution: 0.01 mg/l
pH range: 6 .. 9
Measuring cell:
Sample connection: Tube, inside Ø6 mm, outside max. Ø8 mm
Flow: 35 .. 400 l/h
Pressure: < 6 bars @ 20 °C
Sample temperature: 0 .. 50 °C
conductivity: > 50µS/cm
Control box:
Housing: ABS
Operation & display: Monochrome touch screen, 90 x 50 mm
Protection: IP65
Supply voltage:
- without pH compensation 85 .. 250 VAC, +6/-10%; 40 .. 60 Hz
- with pH compensation: 85 .. 265 VAC, 50 .. 60 Hz
Power input: < 10 VA
Outputs:
- 1/5 x 0/4 .. 20 mA, max. burden 500 Ω, galv. isolated
- 1/4x relay, potential free contact 6A, 250 V, max. 550VA, freely configurable
- automatic sensor cleaning
Input: 1 x digital, function selectable, (NO/NC)
Storage medium: SD card up to 2GB – industrial standard
Ambient temperature: 0 .. 50° C
Ambient humidity: < 90% relative humidity @ 40° C (none condensing)