WAT95: Watt Transducer Vietnam

- High accuracy

- Long term stability

- Time-Division Multiplication principle

            Watt Transducers WAT95 are used to convert single or three phaseunbalance load active power into a proportional load independent DC. Output. Based fully on electronic Time-Division Multiplication measuring principle, the true power of a network with any power factor range are linearly produced by Watt Transducer output.



 

Calibration watt of rated output

Connection

V=110V

V=220V

V=380V

 

I=1A

I=5A

I=1A

I=5A

I=1A

I=5A

Single Phase

100W

500W

200W

1000W

-

-

3phase,3wire

200W

1000W

400W

2000W

600W

3000W

3phase,4wire

200W

1000W

400W

2000W

600W

3000W

Note. V= Line voltage

Equation to calculated measuring range
Measuring range = Calibration watt x PT ratio x CT ratio
Example 3phase,3wire, PT 220V/110V, CT 250/5A, Calibration watt = 1000W
Measuring range = 1000 x 220/110 x 250/5 = 100 KW.

 

Specifications

Input

 

Number of Channel:

3 Channels

Input Type:

Current, Voltage (1 phase,3 phase 3 wire, 3 phase 4 wire)

Input Range:

Current (1, 5 A), Accuracy Class: 0.5

 

Voltage (110, 220, 380 VAC (Line voltage for 3 phase)

Power Consumption:

< 0.2 VA for input current, < 0.4 VA for voltage input

Frequency:

50 Hz.

Analog Output

 

Number of Channel:

1 Channel

Output Type:

Current, Voltage

Output Range:

Current Max 0 to 1 mA (Load Resistance 10 KΩ)

 

Current Max 4 to 20 mA (Load Resistance 600 Ω)

 

Voltage Min 0 to 10 mVDC (Load Resistance 500 Ω)

 

Voltage Min 0 to 100 mVDC (Load Resistance 500 Ω)

 

Voltage Min 0 to 1 VDC (Load Resistance 500 Ω)

 

Voltage Min 0 to 5 VDC (Load Resistance 1 KΩ)

 

Voltage Min 1 to 5 VDC (Load Resistance 1 KΩ)

 

Voltage Min 0 to 10 VDC (Load Resistance 2 KΩ)

Linearity:

< ± 0.5 % of span

Power Requirements

 

Power Supply:

110, 220 VAC

Environmental Limits

 

Operating Temperature:

0 to 55 °C

Operating Humidity:

5 to 95 %RH

Storage Temperature:

0 to 70 °C

Physical Characteristics

 

Dimension:

W132 x H132 x D162 mm.

Mounting:

Wall Mount

Wiring:

Screw Terminals

Protection:

IP20

Warranty

 

Warranty Period:

5 year

Ordering

Ordering Information: Specify Connection, Input voltage, Input current, Output, Power supply
Example WAT95/3 phase 4 wire/380 VAC/5A/4-20 mA/220 VAC

Packagelist

Package Checklist

1. WAT95

Downloads