VAR95: Var Transducer Vietnam
| Voltage Input 110 VAC, 220 VAC, 380 VAC
- Current Input 1 A, 5 A - Analog Output 4-20 mA, 0-5 VDC |
The Var Transducers VAR95 are used to convert single or three phase unbalance load reactive power into a proportional load independent DC. output. Based fully electronic Time-Division Multiplication measuring principle, the reactive power of a network with any power factor range are linearly produced by Var Transducers output.
Calibration var of rated output
| Connection | V=110V | V=220V | V=380V | ||||||
|
|
|
|||||||
| Single Phase |
|
|
|
||||||
| 3phase,3wire |
|
|
|
||||||
| 3phase,4wire |
|
|
|
Note. V= Line voltage
Equation to calculated measuring range
Measuring range = Calibration var x PT ratio x CT ratio
Example 3phase,3wire, PT 220V/110V, CT 250/5A, Calibration var = 1000W
Measuring range = 1000 x (220/110) x (250/5) = 100 Kvar.
|
Input |
|
|---|---|
|
Number of Channel: |
3 Channels |
|
Input Type: |
Current, Voltage (1 phase,3 phase 3 wire, 3 phase 4 wire) |
|
Input Range: |
Current (1, 5 A AC) |
|
Voltage (110, 220, 380 VAC (Line voltage for 3 phase) |
|
|
Power consumption: |
< 0.2 VA for input current, < 0.4 VA for voltage input |
|
Frequency: |
50 Hz. |
|
Analog Input |
|
|---|---|
|
Number of Channel: |
1 Channel |
|
Output Type: |
Current, Voltage |
|
Output Range: |
Current Max (-)1 to 1 mA (Load Resistance 10 KΩ) |
|
Current Max 4 to 20 mA (Load Resistance 600 Ω) |
|
|
Voltage Min 0 to 10 mVDC (Load Resistance 500 Ω) |
|
|
Voltage Min 0 to 100 mVDC (Load Resistance 500 Ω) |
|
|
Voltage Min 0 to 1 VDC (Load Resistance 500 Ω) |
|
|
Voltage Min 0 to 5 VDC (Load Resistance 1 KΩ) |
|
|
Voltage Min 1 to 5 VDC (Load Resistance 1 KΩ) |
|
|
Voltage Min 0 to 10 VDC (Load Resistance 2 KΩ) |
|
|
Linearity: |
< ¾ 0.5% of span |
|
Power Requirements |
|
|---|---|
|
Power Supply: |
110, 220 VAC |
|
Environmental Limits |
|
|---|---|
|
Operating Temperature: |
0 to 55 °C |
|
Operating Humidity: |
5 to 95 %RH |
|
Storage Temperature: |
0 to 70 °C |
|
Physical Characteristics |
|
|---|---|
|
Dimension: |
W132 x H132 x D162 mm. |
|
Mounting: |
Wall Mount |
|
Wiring: |
Screw Terminals |
|
Warranty |
|
|---|---|
|
Warranty Period: |
5 year |
| Ordering Information: | Specify connection, Input voltage, Input current, Output, Power supply |