VAR95: Var Transducer Vietnam
| Voltage Input 110 VAC, 220 VAC, 380 VAC - Current Input 1 A, 5 A - Analog Output 4-20 mA, 0-5 VDC | 
The Var Transducers VAR95 are used to convert single or three phase unbalance load reactive power into a proportional load independent DC. output. Based fully electronic Time-Division Multiplication measuring principle, the reactive power of a network with any power factor range are linearly produced by Var Transducers output.
Calibration var of rated output
| Connection | V=110V | V=220V | V=380V | ||||||
| 
 | 
 | 
 | |||||||
| Single Phase | 
 | 
 | 
 | ||||||
| 3phase,3wire | 
 | 
 | 
 | ||||||
| 3phase,4wire | 
 | 
 | 
 | 
Note. V= Line voltage
Equation to calculated measuring range
Measuring range = Calibration var x PT ratio x CT ratio
Example 3phase,3wire, PT 220V/110V, CT 250/5A, Calibration var = 1000W
Measuring range = 1000 x (220/110) x (250/5) = 100 Kvar.
| Input | |
|---|---|
| Number of Channel: | 3 Channels | 
| Input Type: | Current, Voltage (1 phase,3 phase 3 wire, 3 phase 4 wire) | 
| Input Range: | Current (1, 5 A AC) | 
| Voltage (110, 220, 380 VAC (Line voltage for 3 phase) | |
| Power consumption: | < 0.2 VA for input current, < 0.4 VA for voltage input | 
| Frequency: | 50 Hz. | 
| Analog Input | |
|---|---|
| Number of Channel: | 1 Channel | 
| Output Type: | Current, Voltage | 
| Output Range: | Current Max (-)1 to 1 mA (Load Resistance 10 KΩ) | 
| Current Max 4 to 20 mA (Load Resistance 600 Ω) | |
| Voltage Min 0 to 10 mVDC (Load Resistance 500 Ω) | |
| Voltage Min 0 to 100 mVDC (Load Resistance 500 Ω) | |
| Voltage Min 0 to 1 VDC (Load Resistance 500 Ω) | |
| Voltage Min 0 to 5 VDC (Load Resistance 1 KΩ) | |
| Voltage Min 1 to 5 VDC (Load Resistance 1 KΩ) | |
| Voltage Min 0 to 10 VDC (Load Resistance 2 KΩ) | |
| Linearity: | < ¾ 0.5% of span | 
| Power Requirements | |
|---|---|
| Power Supply: | 110, 220 VAC | 
| Environmental Limits | |
|---|---|
| Operating Temperature: | 0 to 55 °C | 
| Operating Humidity: | 5 to 95 %RH | 
| Storage Temperature: | 0 to 70 °C | 
| Physical Characteristics | |
|---|---|
| Dimension: | W132 x H132 x D162 mm. | 
| Mounting: | Wall Mount | 
| Wiring: | Screw Terminals | 
| Warranty | |
|---|---|
| Warranty Period: | 5 year | 
| Ordering Information: | Specify connection, Input voltage, Input current, Output, Power supply | 
| Example | VAR95/3 phase 4 wire/380 VAC./5A/4-20 mA/220 VAC | 
Package Checklist