VAR95: Var Transducer Vietnam
Voltage Input 110 VAC, 220 VAC, 380 VAC
- Current Input 1 A, 5 A - Analog Output 4-20 mA, 0-5 VDC |
The Var Transducers VAR95 are used to convert single or three phase unbalance load reactive power into a proportional load independent DC. output. Based fully electronic Time-Division Multiplication measuring principle, the reactive power of a network with any power factor range are linearly produced by Var Transducers output.
Calibration var of rated output
Connection | V=110V | V=220V | V=380V | ||||||
|
|
|
|||||||
Single Phase |
|
|
|
||||||
3phase,3wire |
|
|
|
||||||
3phase,4wire |
|
|
|
Note. V= Line voltage
Equation to calculated measuring range
Measuring range = Calibration var x PT ratio x CT ratio
Example 3phase,3wire, PT 220V/110V, CT 250/5A, Calibration var = 1000W
Measuring range = 1000 x (220/110) x (250/5) = 100 Kvar.
Input |
|
---|---|
Number of Channel: |
3 Channels |
Input Type: |
Current, Voltage (1 phase,3 phase 3 wire, 3 phase 4 wire) |
Input Range: |
Current (1, 5 A AC) |
Voltage (110, 220, 380 VAC (Line voltage for 3 phase) |
|
Power consumption: |
< 0.2 VA for input current, < 0.4 VA for voltage input |
Frequency: |
50 Hz. |
Analog Input |
|
---|---|
Number of Channel: |
1 Channel |
Output Type: |
Current, Voltage |
Output Range: |
Current Max (-)1 to 1 mA (Load Resistance 10 KΩ) |
Current Max 4 to 20 mA (Load Resistance 600 Ω) |
|
Voltage Min 0 to 10 mVDC (Load Resistance 500 Ω) |
|
Voltage Min 0 to 100 mVDC (Load Resistance 500 Ω) |
|
Voltage Min 0 to 1 VDC (Load Resistance 500 Ω) |
|
Voltage Min 0 to 5 VDC (Load Resistance 1 KΩ) |
|
Voltage Min 1 to 5 VDC (Load Resistance 1 KΩ) |
|
Voltage Min 0 to 10 VDC (Load Resistance 2 KΩ) |
|
Linearity: |
< ¾ 0.5% of span |
Power Requirements |
|
---|---|
Power Supply: |
110, 220 VAC |
Environmental Limits |
|
---|---|
Operating Temperature: |
0 to 55 °C |
Operating Humidity: |
5 to 95 %RH |
Storage Temperature: |
0 to 70 °C |
Physical Characteristics |
|
---|---|
Dimension: |
W132 x H132 x D162 mm. |
Mounting: |
Wall Mount |
Wiring: |
Screw Terminals |
Warranty |
|
---|---|
Warranty Period: |
5 year |
Ordering Information: | Specify connection, Input voltage, Input current, Output, Power supply |
Example | VAR95/3 phase 4 wire/380 VAC./5A/4-20 mA/220 VAC |
Package Checklist
1. VAR95